← Back to Rooms
🎙️ B304

VO Live

Professional voiceover booth engineered for NC-20 silence. Motorized acoustic curtain provides adjustable RT60 between dead (0.20s) and live (0.27s) settings.

Floor Area
5.31 m²
Volume
14.6 m³
NC Target
NC-20
RT60 @ 1kHz
0.2s

Dimensions & Geometry

Room Dimensions

Width3.01 m avg (301 cm avg)
Depth1.76 m
Height2.75 m (acoustic ceiling)
Area5.31 m²
Volume14.6 m³ (5.31 × 2.75)
Flooringvinyl

Boundaries

northconcrete north
westconcrete diagonal
eastbuffer spine
southpartition to Control

Door

DoorD3 — VO Live
Size80 × 220 cm
STC45
SwingN into VO Live

Room Floor Plan

This room is highlighted on the full zone plan. All positions from SSOT → DXF.

BUFFER STC55 COL-W COL-E D190×220 STC50D290×220 STC45D380×220 STC45D490×220 STC40 W1 80×50 VO Live B304 5.31 m² · NC-20 Control Room B311 5.47 m² · NC-25 Video/Podcast Studio B312-1 11.23 m² · NC-25 Editing Suite B312-2 8.56 m² · NC-35 207152039019723860 cm (north wall inner)229175448 cm (diagonal) D1 STC50 D2 STC45 D3 STC45 D4 STC40 W1 STC50 Column Door swing N

VO Live Infrastructure

Lighting

Main2× 200W LED panel 2700–3500K tunable

Acoustic Treatment

walls70% coverage with 50mm rockwool panels (fabric wrapped)
ceilingRockfon Sonar E (NRC 0.90) — full coverage in 600x600mm T-grid at 2.75m
ceiling above100mm Rockwool ProRox SL 930 batts on top of tiles
bassTraps4x corner-mounted, floor-to-acoustic-ceiling (2.75m)
floorvinyl on float floor

RT60 Analysis

Target range: 0.15s – 0.25s · Achieved @ 1kHz: 0.2s

FrequencyTargetAchievedDiffStatus
125 Hz0.25s0.28s0.03s
250 Hz0.22s0.23s0.01s
500 Hz0.20s0.20s0.00s
1000 Hz0.18s0.19s0.01s
2000 Hz0.18s0.18s0.00s
4000 Hz0.18s0.17s-0.01s

Modal Analysis

Schroeder frequency: 234 Hz · Dimensions: 3.01 × 1.762 × 2.75 m

ModeLength (1.762m)Width (3.01m)Height (2.75m)
n=1 97.4 Hz 57.0 Hz 62.4 Hz
n=2 114.0 Hz 194.7 Hz 124.7 Hz
n=3 170.9 Hz 292.0 Hz 187.1 Hz
n=4 227.9 Hz 249.5 Hz
n=5 284.9 Hz 311.8 Hz

Noise Criteria Budget

NC TargetNC-20
NC-20 target assumes VRF unit off or on minimum fan speed during recording. Realistic with HVAC running: NC-25–NC-30 pending final MEP design.
HVAC MaxNC-12
Transmitted MaxNC-12
Design Margin5 dB

Acceptance Criteria

NC Pass≤ 20
NC Conditional≤ 23
RT60 Range0.15s – 0.3s
Min STC53